What is PUE?

A data centre’s total energy divided by the energy its IT uses.

How is it worked out?

Divide the total by the IT energy, both in kWh for the same year. At 1.00 every kWh would reach the IT; at 1.50, half as much again goes elsewhere.

  • The formula is total data centre energy over IT energy. source

  • The task force recommends a year of energy, in kWh, as the measure. source

  • A year means twelve consecutive months of readings. source

What counts as IT energy?

What the servers, storage, network and telecom equipment use.

  • Servers, networking, storage, and the telecom equipment of a telecom data centre, over a year. source

What counts as the total?

Everything that crosses the data centre’s boundary.

  • In a building that is only a data centre, the total is all the energy on its utility bills. source

  • UPS, transformers, generators, wiring and lighting count in the total; so do cooling, security and building controls. source

Where should the IT meter sit?

At the UPS output at least; the closer to the servers, the better the reading.

  • Category 0: peak kW, IT read at the UPS output. source

  • Category 1: a year of kWh at the UPS output. source

  • Category 2: at the PDU output. source

  • Category 3: where each IT device plugs in. source

How is a PUE written?

With its category as a subscript: PUE₁ 1.62, not PUE 1.62.

  • Without the subscript, a PUE does not follow the recommendations. source

  • Category 0 is for sites on electricity alone. source

  • A site that also buys fuel or chilled water weights each before adding it. source

Does renewable power lower it?

No. PUE measures how energy is used inside the data centre, wherever it comes from.

  • A site on the grid and one on renewables that use energy alike have the same PUE. source

Can two sites be compared?

With care: first rule out reliability and climate.

  • Reliability and climate change a PUE; rule them out first. source

  • PUE says nothing about how efficient the IT equipment itself is. source

Who wrote these rules?

A task force of eight industry and government bodies, in 2011, The Green Grid and ASHRAE among them.

  • The paper names all eight. source